PV inverter SUN2000-30KTL-A/33KTL-A/40KTL |
Technical Specifications | SUN2000-30KTL-A |
---|---|
Efficiency | |
Max. Efficiency | 98.6% |
European Efficiency | 98.3% |
Input | |
Max. DC Usable Power | 30,600 W |
Max. Input Voltage | 1,000 V |
Max. Current per MPPT | 23 A |
Max. Short Circuit Current per MPPT | 32 A |
Min. Operating Voltage / Start Input Voltage | 200 V / 250 V |
Full Power MPPT Voltage Range | 580 V ~ 850 V |
MPPT Operating Voltage Range | 200 V ~ 950 V |
Rated Input Voltage | 720 V |
Max. Number of Inputs | 6 |
Number of MPP Trackers | 3 |
Output | |
Rated AC Active Power | 30,000 W |
Max. AC Apparent Power | 33,000 VA |
Max. AC Active Power (cosφ=1) | 30,000 W |
Rated Output Voltage | 277 V / 480 V, 3W+PE |
Rated AC Grid Frequency | 50 Hz / 60 Hz |
Max. Output Current | 40 A |
Adjustable Power Factor | 0.8 LG ... 0.8 LD |
Max. Total Harmonic Distortion | <3% |
Protection | |
Input-side Disconnection Device | Yes |
Anti-Islanding Protection | Yes |
AC Overcurrent Protection | Yes |
DC Overcurrent Protection | Fuseless |
DC Reverse-Polarity Protection | Yes |
PV-array String Fault Monitoring | Yes |
DC Surge Arrester | Type II |
AC Surge Arrester | Type II |
Insulation Monitoring | Yes |
Residual Current Detection | Yes |
Communication | |
Display | LED Indicators |
RS485 | Yes |
USB / Bluetooth + APP | Yes |
Power Line Communication (PLC) | Optional |
General | |
Dimensions(W×H×D) | 550×770×270 mm (21.7×30.3×10.6 inch) |
Weight | 50 kg (110 lb) |
Operation Temperature Range | -25 °C ~ +60 °C (-13°F ~ +140°F) |
Cooling | Natural Convection |
Operating Altitude | 4,000 m (13,123 ft) |
Relative Humidity | 0 ~ 100% |
DC Connector | Amphenol H4 |
AC Connector | Waterproof PG Terminal + OT Connector |
Protection Rating | IP65 |
Internal Consumption at Night | <1 W |
Topology | Transformerless |
Noise Emission (Typical) | <33 dB |
Standards Compliance | |
Safety/EMC | EN 61000-3, EN 61000-6, EN/IEC 62109-1, EN/IEC 62109-2, IEC 60529 |
Grid Code | IEC 61727, IEC 62116, IEC 61683, IEC 60068-2, RD1669, PEA 2013, Resolution No. 07, NRS 097-2-1 |
Technical Specifications | SUN2000-30KTL-A |
---|---|
Efficiency | |
Max. Efficiency | 98.6% |
European Efficiency | 98.3% |
Input | |
Max. DC Usable Power | 30,600 W |
Max. Input Voltage | 1,000 V |
Max. Current per MPPT | 23 A |
Max. Short Circuit Current per MPPT | 32 A |
Min. Operating Voltage / Start Input Voltage | 200 V / 250 V |
Full Power MPPT Voltage Range | 480 V ~ 800 V |
MPPT Operating Voltage Range | 200 V ~ 950 V |
Rated Input Voltage | 620 V |
Max. Number of Inputs | 6 |
Number of MPP Trackers | 3 |
Output | |
Rated AC Active Power | 30,000 W |
Max. AC Apparent Power | 33,000 VA |
Max. AC Active Power (cosφ=1) | 30,000 W |
Rated Output Voltage | 220V / 380V, 230V / 400V, 3W+N+PE |
Rated AC Grid Frequency | 50 Hz / 60 Hz |
Max. Output Current | 48 A |
Adjustable Power Factor | 0.8 LG ... 0.8 LD |
Max. Total Harmonic Distortion | <3% |
Protection | |
Input-side Disconnection Device | Yes |
Anti-Islanding Protection | Yes |
AC Overcurrent Protection | Yes |
DC Overcurrent Protection | Fuseless |
DC Reverse-Polarity Protection | Yes |
PV-array String Fault Monitoring | Yes |
DC Surge Arrester | Type II |
AC Surge Arrester | Type II |
Insulation Monitoring | Yes |
Residual Current Detection | Yes |
Communication | |
Display | LED Indicators |
RS485 | Yes |
USB / Bluetooth + APP | Yes |
Power Line Communication (PLC) | Optional |
General | |
Dimensions(W×H×D) | 550×770×270 mm (21.7×30.3×10.6 inch) |
Weight | 50 kg (110 lb) |
Operation Temperature Range | -25 °C ~ +60 °C (-13°F ~ +140°F) |
Cooling | Natural Convection |
Operating Altitude | 4,000 m (13,123 ft) |
Relative Humidity | 0 ~ 100% |
DC Connector | Amphenol H4 |
AC Connector | Waterproof PG Terminal + OT Connector |
Protection Rating | IP65 |
Internal Consumption at Night | <1 W |
Topology | Transformerless |
Noise Emission (Typical) | <33 dB |
Standards Compliance | |
Safety/EMC | EN 61000-3, EN 61000-6, EN/IEC 62109-1, EN/IEC 62109-2, IEC 60529 |
Grid Code | IEC61727, IEC62116, IEC 61683, IEC 60068-2, EN50438, CGC/GF 035-2013, GB/T 19964-2012, NB/T 32004-2013, VDE-AR-N4105, VDE0126-1-1, BDEW 2008, G59/3, AS4777, UTE C 15-712-1, C10/11, RD1669, PEA 2013, Resolution No. 07, NRS 097 |